- Implementation of large capacity in small, lightweight form
- Bolt, DIN Rail attachment method
- High insulation between input / output
- C-R Snubber, Zero Cross function
Suffix codeDimensionEquivalent CircuitConnectionInput/LoderInstallationHeat SinkPrecautions during the use of Heat Sink
The order from the left is the order in which the information is displayed at the bottom.
If you cancel the check, the information will be excluded, and if you check, it will be
printed out.
▍Installation
Please make intervals more than the sizes in the following picture.
Please install wiring duct less than half the height of the heat sink
to prevent the flow of air.
It is good to use Hanyoung Nux's HSR in lower than ambient
temperature 40℃ so, please use it lower than standard temperature.
When installing the HSR, be sure to install the heat sink in the vertical direction.
Unavoidably, if installed horizontally, the performance of the product will drop below 50 %
Input terminal wiring
1 X 0.5 mm² (1 X AWG20) or larger
1 X 1.5 mm² (1 X AWG16) or less than 2 X 1.5 mm² (2 X AWG16)
Output terminal wiring
1 X 1.5mm² (1 X AWG16) or larger
1 X 16 mm² (1 X AWG6) or less than 2 X 6 mm² (2 X AWG10)
※ Connect the wiring suitable for the load current capacity
to the output terminal.