HSR-2E series Single-phase 2-wire control overcurrent sensing solid-state relay
- Accurate under/overload detection in On/Off cycle control situations.
- True RMS current measurement
- Display of operation status, output status, alarm LED
- Medium alarm, light alarm relay contact output
- Integrated heat sink
- Detection of TRIAC SHORT, load disconnection, overcurrent, and undercurrent
- 2-wire cutoff method (simultaneous control of two lines of single phase)
- Alarm record function (type of alarm and max current of 20ea)
- Application of bimetal at 60℃, 80℃

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Manual Mode Description (Stand Alone Control)

※ Cannot be used except for adjusting the amount of output

Types of

Operation

How to operate

Function Description

Switch

operation

no manipulation

Output amount: 0%

Jog Push Down

Output amount: 100%

Jog

operation

Turn to the right

Increase output amount: 0 ~ 100%

Turn to the left

Decrease output amount: 100 ~ 0%

Incremental output control method

Operation method of manual mode

Output control methods

1. Variable cycle On/Off control

User Sub Menu -> om -> mU setting

Method of ending Stand Alone Control

2. Fixed cycle On/Off control

When external control input is applied, it immediately switches to automatic operation mode.

If the switch is operated twice in a row, it switches to automatic operation mode.