NP200 Programmable Temperature Controller
- Multi input/output, high accuracy (+/-0.1%)
- 30 patterns, 300 segments (1 pattern / 99 segments)
- Heat & cooling PID control
- 3 level PID selection (4 PID groups)
- PID auto-tuning mode 2 types
- Digital input(DI) 7 contacts, User output(UO) 10 contacts
- Communication fuction (RS485/422)

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

■ Input Specification

Input

Multi range type (Refer to “Input type Kinds and Range”)

Sampling time

100 ms

Input resolution

Basically for the numbers below the decimal point

Input impedance

T/C & mV input: 1 MΩ min, d.c. mV input: approx 1 MΩ

Allowable signal source resistance

T/C: Max 250 Ω, DC mV/V: Less than 2 kΩ

Allowable wiring resistance

RTD input: Less than 150 Ω/ 1 wire

Allowable input voltage

DC mV/Thermocouple/RTD: ±10 V, DC V: ±20 V

Noise removal rate

NMRR : more than 40 dB (50 / 60 Hz ±1 %) CMRR : more than 120 dB

Standard

Thermocouple/RTD (KS / IEC / DIN)

Input signal break detection

(Burn - out)

T/C: Up Scale / Down Scale

RTD: Up Scale

Detected voltage in signal break: Approx. 50 nA

Accuracy

Max scale 0.1 %

■ Output

◾ Output type

Relay output

Contact capacity : 240 V a.c. 3 A, 30 V d.c. 3 A (registance).

Composition of contac t : 1c

Output operation : time proportioned or ON/OFF

Time proportion cycle time : 1 ~ 1000 s

Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L). (Trial for MAN / AT is possible).

ON/OFF hysterisis : 0 ~ 100 %

Time resolution : the small one in either 0.1 % or 10 ms

SSR output

ON voltage : more than 25 V d.c. (Load resistance more than 600 Ω when cut off happens there’s limit on electric current of around 30 mA)

OFF voltage : less than 0.1 V d.c.

Output operation: Time proportioned

Cycle time : 1 ~ 1000 s

Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L). (Trial for MAN / AT is possible).

Time resolution : the small one in either 0.1 % or 10 ms

SCR output

(4~20 mA d.c.)

Output current range : 4 ~ 2 mA

DC output renewal cycle : 100 ms

Load resistance: less than 600 Ω

Output operation : consecutive PID

Output ripple : less than 0.1 % of FS. (p-p) (150 Hz)

Accuracy : ±0.3 % of FS. (range from 4 ~ 20mA DC) Resolution : around 3,000

Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L).(Trial for MAN / AT is possible).

Manual operation

Conversion to MANUAL operation is possible at the number 5 of operation screen and communication.

A → M: output tracking M → A: bumpless

■ Certifications

Certification

UL (ongoing)

C-UL (ongoing)

CE (ongoing)

■ Retransmission output

Current output

Current output range: 4 - 20 mA d.c.

Resistance load: less than 600 Ω

Accuracy : ±0. % of FS. (4 - 20 mA d.c.)

Resolution : Approx. 3,000

Output ripple : Max 0.1 % of FS. (p-p) (150 Hz)

Output renewal cycle time : 100 ms

Retransmission output

Retransmission signal: PV (Process value) / SV (Set value) / MV (Volume of output) / SPS (Power supply for sensor)

Scaling: PV (Process value) / SV (Set value)

  • SPS(Power supply for sensor): Retransmission output of PV/SV/MV can not be used when you use SPS.

■ Interface

Standard

EIA RS485

Number of devices

31. Address setting: 1~99 range

Communication type

2 wire or 4 wire half-duplex

Synchronization

Start – stop synchronous mode

Communication order

None

Communication distance

Max 1.2 km

Communication rate

600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 bps

Start Bit

1 Bit

Data length

7 or 8 Bit

Parity

None, Even, Odd

Stop Bit

1 or 2 Bit

Protocol

PC-LINK, PC-LK-S, MODBUS ASCII, MODBUS RTU

Response time

Handling time + (RP.T X 10 ms)

■ Power Supply

Power supply voltage

100 - 240 V a.c. (90V ~ 250V)

Frequency

50 - 60 Hz

Power Consumption

Max 6.0W / MAX 10 VA

Insulation resistance

20 MΩ min(at 500V d.c.) : Between primary terminal and secondary terminal

Between primary terminal and ground

Between ground and secondary terminal

Dielectric Strength

2300V a.c. 50/60 Hz for 1 minute : Between primary terminal and secondary terminal

Between primary terminal and ground

1500V a.c. 50/60 Hz for 1 minute : Between F.G terminal and secondary terminal

Power supply for sensor

24 V d.c. 20 mA Max (select between retransmission output or SPS)

■ Function

Measuring Input

Bias

-100.0 ~ 100.0 % for measuring input range.

Valid setting a correction value

Scaling

According to setting of SL-H, SL-L of measuring range, scaling is available.

Input filter

OFF, 1 ~ 120 s

Control

Fix SV

4 kinds

Pattern

30 Patterns, 99 segments are available in each pattern

Segment

300 Segments

PID Group

4 kinds

Auto Tuning

According to SV, AT is operating.

(Select STD or low PV)

Proportional band (P)

0.1 % ~ 999.9 %

Integral time (I)

OFF, 1 ~ 6000sec

Differential time (D)

OFF, 1 ~ 6000sec

ON/OFF control

Select ON/OFF control in output group

PID converter

Level PID/Segment PID selectable

Manual reset

-0.5 ~ 105.0 %. 〔Valid when I=OFF〕

Direct/reverse action

Select direct or reverse action in output group

Emergency output

-0.5 ~ 105.0 % of output value

ON/OFF hysteresis

0.0 ~ 100.0 % of range (in case of ON/OFF control, it is up to hysteresis value in output group.)

Heating/cooling hysteresis

-100.0 ~ 50.0 % of output value

Auto/Man

Convert at the 5th operation screen

Anti reset wind up (ARW)

AUTO, 50.0 ~ 200.0 % at the PID group

Retransmission

output

Retransmission signal

PV, SV, MV, SPS (select TRANS in retransmission group)

Scaling

Setting PV, SV

Alarm

Setting points

Max 10 points

Type of alarm

High/low alarm, High/low deviation alarm

Setting range

Process alarm: 0~100 % of range

Deviation alarm: -100~100 % of range

Alarm hysteresis

0.0~100.0 % of instrument range

■ Condition for transportation & storage

Temperature

-25 ~ 70 ℃

Humidity

5 ~ 95 % RH (no icing)

Shock

Fall from less than 1m

■ Structure

Material

Plastic case

Weight

696 g (including bracket and box)

Panel cutout

92(W) X 92(H)

■ Operating Environment

Setting surroundings

Consecutive vibration : vibration width is less than 1.2mm (5 ~14 Hz)

Consecutive vibration : 4.9 m/s² (4 ~ 150 Hz)

Short time vibration : 14.7 m/s² less than 15 seconds (each 3 directions)

Shock : 147 m/s² less than 11ms (3 times at each 3 directions)

Conditions for normal operation

Temperature : 0 ~ 50℃

Humidity : 35 ~ 85 % RH (no icing)

Magnetic range : less than 400 AT/m

Warm Up Time : more than 30 minutes

Effects of temperature

in the surrounding environment

T/C voltage input : ±1 ㎶/℃ or ±0.01 % of FS/℃

RTD input : less than ±0.05 FS/℃

Analog output : less than ±0.05 % of FS/℃ (consecutive output)

Effects of voltage fluctuation rate

Analog input : ±1 ㎶/10V or ±0.01 % of FS/10V

Analog input : less than ±0.05 % of FS/10V

▍Suffix code

Model

Code

Function

NP200 –

Programmable Controller (96 X 96 mm)

Control Type

0

 

Universal Type

1

 

Heating/Cooling Type

Option

0

None

1

RS422 / 485 (Communication Function)

2

DI 4 Points(External Signal Input)

3

RS422 / 485(Communication Function), DI 4Points

  • DI 1~3 Standard, DI 4~7 Option

▍Dimension

[Unit : ㎜]

■ Dimension

Dimension

■ Panel Cutout

Panel Cutout