TH510 Programmable temperature · humidity controller
- High precision control
- Various alarm functions
- Detachable, expandable structure
- Temperature, humidity independent PID control
- Built-in communication function (RS485)
- Digital Recorder function (internal memory, SD card storage)
- Contact input (DI) with up to 32 contacts, contact output (DO) with up to 32 contacts
- Color TFT LCD screen with touch panel (640 * 480 resolution)
CE

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

■ Range configuration by input type

Input type

Temperature

Humidity

Measuring range (℃)

accuracy

Measuring range (%RH)

accuracy

Thermoresistor

(RTD)

Pt100 Ω

Pt-1

-100.0 ~ 300.0

±0.1 % of F.S

±1 Digit

0.0 ~ 100.0

±1 % of F.S

±1 Digit

Pt-2

-100.00 ~ 150.00

KPt100 Ω

KPt-1

-100.0 ~ 300.0

KPt-2

-100.00 ~ 150.00

DC voltage

(VDC)

1 - 5 V

-100.0 ~ 300.0

±0.1 % of F.S

±1 Digit

0 - 30 V

-100.0 ~ 300.0

■ Power input

Power voltage

100 – 240 V a.c. Voltage regulation ±10 %

Power frequency

50 - 60 ㎐

Power consumption

30 VA max

Max. rating of internal fuse

250 V a.c.

Dielectric strength

Between 1st and 2nd terminals : Min. 1500 V AC for 1 min

Between 1st and FG terminals : Min. 1500 V AC for 1 min

Between 2nd and FG terminals : Min. 1500 V AC for 1 min

Insulation resistance

20 ㏁ or 500 V DC between power and FG terminals

■ Sensor input

Input type

2 types of thermoresistor (Pt-100, KPt-100), 2 types of DC voltage (1 - 5 V, 0 - 30 V)

Sampling cycle

250 ms

Measured current of

thermoresistor(RTD)

Approx. 0.21 mA

Input resistance

DC voltage : 1 ㏁ or more

Allowable wire resistance

Thermoresistor : Max. 10Ω/wire, DC voltage : 2 ㏀ or less

Influence of wire resistance

Thermoresistor : ±0.3 ℃/10 Ω (3 wires must have the same wire resistance)

Allowable input voltage

DC voltage : ±33 V DC or less

Detection of sensor

disconnection(Burn-out)

UP-Scale for disconnection

■ Output specifications

Contact output (DO)

Up to 32 relay

A Contact

30 V d.c. 3 A max, 250 V a.c. 3 A

B Contact

NO : 30 V d.c. 5 A max, 250 V a.c. 5 A

Control output

SSRoutput

ON : 18 V DC Pulse voltage(800 Ω or more load resistance)

SCRoutput

4 - 20 mA DC (600 Ω or less load resistance)

Transmission output

Current output

4 - 20 mA DC

Load resistance

600 Ω or less load resistance

Output limit

-5.00 - 105.00 %

Output type

Specific value(PV), Setting value(SV), Output(MV), and random

Refresh interval

250 ms

■ Contact input

Max. number of input

32 Contacts

Input type

No-voltage contact input

ON/OFF sensing resistor

Minimum 1㏀ and less: On, maximum 10㏀ and more: Off recognition

Min. sensing time

0.25 sec

Operational conditions

During operation/Always

Contact function

Operation and stop/hold/step by DI ; User can define error screen.

■ Communication specifications

Applied standard

RS485

Max. connection number

1:32 (address 1 ~ 99)

Communication type

2-wire

Synchronization

Asynchronous

Communication distance

Approx. 1.2 km or less

Communication speed

9600, 19200, 38400, 57600, 115200 bps

Data Length

7/8 bits

Parity Bit

NONE / EVEN / ODD

Stop Bit

1/2 bit(s)

Protocol

PC-Link / PC-Link+SUM / MODBUS ASC / MODBUS RTU

Response Time

0 - 100 ms

■ Control function

Input

Input calibration (Sensor bias)

1 Temperature contact : EUS(0 ~ 100 %)

1 Humidity contact : EUS(0 ~ 100 %)

Dry/wet-bulb sensor compensation

Compensate the dry/wet sensor difference after removing the gauze of the wet-bulb sensor.

Scaling

DC voltage(VDC) : Input scaling according to conversion range

Input filter(LPF)

0 ~ 120 sec

Control mode

Operation type

Constant-value / Program control

Control output

Temperature control output

SSR output or SCR (4 - 20 mA DC) output

Humidity control output

Control operation

Pattern

100 patterns(1 pattern/100 segments)

Segment

2000 segments

PID Group

16 groups (temperature 4 zones X humidity 4 zones)

Auto tuning

Auto tuning according to target setting value

Proportional band

0.00 ~ 100.00 % (For 0.00 %, ON/OFF control)

Integral time

0.0 ~ 3,000 sec (OFF when 0 sec)

Derivative time

ON/OFF control

Set 0.0 to proportional band(PB)

Normal Open/Normal Close

According to selection of Normal Open / Normal Close for control output

Hysteresis

EUS (0 ~ 100 %)

Transmission output

Temperature, Humidity

4 - 20 mA d.c.

Specific value(PV), Setting value(SV) and Output(MV)

Scaling

Auto scaling for defined upper/lower limit range

(4 - 20 mA DC)

Alarm setting

Alarm setting

System alarm : 8 points

Assign 4 of 8 pattern alarms to a pattern

Alarm type

Absolute high/low limit, deviation high/low limit, in range/out of range

(alarm direction, hold)

Absolute alarm setting range

EU (0 ~ 100 %)

Offset information setting range

EUS (-100 ~ 100 %)

Hysteresis

EUS (0 ~ 100 %)

■ Display specifications

Display

TFT color LCD (115.2 × 86.4 mm)

Number of Pixels

640 × 480 pixel

Back light

LED back light

Life cycle of back light

Approx. 40,000 h

Touch type

Resistive type (4 Wires)

Language

Korean/English/Chinese(Simplified)

■ Memory specifications

Internal memory

Non-volatile memory : 80 MB – Saving of 15 days at 1 S interval

External memory

SD card(2 GB) : Saving of 1 year at 1 S interval

Saving interval

1 ~ 360 sec

Memory information

Program information, setting value, recovery, and temperature setting/ specific/output value

■ Use environment

Ambient temperature

0 ~ 50 ℃

Temperature fluctuation

10 ℃/h or less

Ambient humidity

20 ~ 90 % RH (Without condensation)

Magnetic field

400 A/m or less

Altitude

2,000 m or less from the sea

Weight

Approx. 1.32 kg

■ Storage environment

Ambient temperature

-20 ~ 70 ℃

Temperature fluctuation

20 ℃/h or less

Ambient humidity

5 - 95 % RH (Without condensation)

■ Influence of ambient temperature

DC voltage

±0.003 % of F.S / ℃

Thermoresistor sensor

±0.03 ℃/℃

■ Approval

Approval

CE