ND4 Analog temperature controller
- Simple temperature set up
- Proportioning control or ON/OFF control
- Burn out (Output OFF when sensor disconnected)
- Plug in type(simple correcting, checking and exchanging)

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

Power supply voltage

220 V a.c. 60 Hz

Voltage variation rate

± 10 % of supply voltage

Power Consumption

3 VA

Input

Thermocouple, RTD (Pt 100 Ω)

Adjusting Sensitivity

0.2 % (fixed) of Max. Range

Control Method

Proportional control, ON/OFF control

Setting Method

Analog setting

Control output

▪Relay Output : 250 V a.c. 3 A (Resistive Load) SPDT

▪SSR Output : Voltage pulse 12 V d.c. (Resistive Load Min. 800 Ω)

Setting Accuracy

Same as display value without relative error

Proportional Band

3 % of FS (fixed)

Relay Life Expectancy

▪Mechanical : Min.10 millions times.

▪Electrical : Min. 100 thousands times. (250 V a.c. 5 A Resistive Load)

Sampling Cycle

▪Relay Output : 20 sec

▪SSR Output : 2 sec

External Input Resistance

▪Thermocouple: Max. 100 Ω

▪RTD: Max. 10 Ω per 1 wire (the resistance of each wire should be the same.)

Dielectric strength

2000 V a.c. 60 Hz for 1min

Ambient Temperature · Humidity

0 - 50 ℃, 35 ~ 85 % RH (Without condensation)

Vibration resistance

Durability

2 - 55 Hz, X·Y·Z in each direction for 10 min

Malfunction

10 - 55 Hz, 0.76 mm, X·Y·Z in each direction for 2 min

Shock resist

Durability

300 m/s²

Malfunction

200 m/s²

Weight

Approx. 220 (including installation adaptor)

▍Suffix code

Model

Code

Content

ND4 -

Non-indicating type temperature controller

Control type

F

 

 

 

 

 

ON/OFF control (2 position control)

P

 

 

 

 

 

Proportional control

Input

K

 

 

 

 

K thermocouple

P

 

 

 

 

RTD Pt100 Ω (IEC)

Control output

M

 

 

 

Relay

Control operation

R

 

 

Reverse control (Heating control)

D

 

 

Direct control (Cooling control)

Range code

 

 

Select the standard range code

Terminal structure

T

Terminal type

▍Dimension & Panel cutout

[Unit : ㎜]

■ Dimension

◾ Socket Type

Socket

◾ Terminal Type

Terminal

■ Panel cutout

※ Socket type and terminal type panel cutouts are the same.

Panel cutout