▍Specification
|
Model
|
HY-48
|
HY-72
|
HY-8000
|
HY-8200
|
|
Input
|
Thermocouple input
|
TC-K
|
|
Reference junction
compensation accuracy
|
±1.5 ℃ (within -10 ~ 50 ℃)
|
|
RTD input
|
Pt100 Ω
|
|
Allowable wiring resistance
|
10 Ω or less, but the resistance between 3 wires should be the same
|
|
Input sampling cycle
|
500 ms
|
|
Control
output
|
Output type
|
Relay : 1C, 250 V a.c. 5A
|
|
Control type
|
ON/OFF control, Proportional control (Selective by Internal DIP switch)
|
|
Proportional band
|
1 ~ 10 ℃
|
|
Manual reset (MR)
|
0 ~ 100 %
|
|
Control cycle
|
20 sec
|
|
Hysteresis
|
2 ℃
|
|
Output acting
|
Reverse acting(heating)
|
|
Alarm
output
|
Alarm type
|
Model HY-8200 only. High limit alarm
|
|
Output type
|
Relay : 1C, 250 V a.c. 5A
|
|
Hysteresis
|
2 ℃
|
|
Power
supply
|
Power supply voltage
|
100 - 240V a.c. 50 - 60Hz
|
|
Voltage fluctuation rate
|
± 10% of power supply voltage
|
|
Insulation Resistance
|
Min. 20 MΩ, 500 V d.c.
|
|
Dielectric strength
|
3,000 V a.c., 50/60 Hz for 1 minute (between 1st and 2nd terminal)
|
|
Power consumption
|
2.1VA
|
2.5VA
|
2.6VA
|
3.6VA
|
|
Display accuracy
|
±1% of FS ±1 Digit
|
|
Ambient temperature/humidity
|
0 ~ 50 ℃, 35 ~ 85 % RH (without condensation)
|
|
Storage temperature
|
-25 ~ 65 ℃
|
|
Weight (g)
|
156
|
164
|
222
|
232
|
▍Suffix code
|
Model
|
Code
|
Description
|
|
HY-
|
-
|
|
|
|
|
|
|
Digital temperature controller
|
|
Description
|
48
|
|
|
|
|
|
|
48(W) X 48(H) mm
|
|
72
|
|
|
|
|
|
|
72(W) X 72(H) mm
|
|
8000
|
|
|
|
|
|
|
96(W) X 96(H) mm
|
|
8200
|
|
|
|
|
|
|
96(W) X 96(H) mm
|
|
Input
|
K
|
|
|
|
|
|
K thermocouple
|
|
P
|
|
|
|
|
|
RTD, Pt 100 Ω (IEC)
|
|
Control output
|
M
|
|
|
|
|
Relay contact output
|
|
Alarm output
|
N
|
|
|
|
None
|
|
O
|
|
|
|
High alarm (Only for HY-8200 model)
|
|
Control direction
|
R
|
|
|
Reverse action (Heating control)
|
|
Power supply voltage
|
A
|
|
100 - 240 V a.c. 50 - 60 Hz
|
|
Range code
|
|
Refer to the range and input code
|
- Alarm output is available only for HY-8200 model
- Default set by Proportional control.
▍Dimension and panel cutput
[Unit : mm]
|
Model
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H
|
I
|
|
HY-48
|
48
|
48
|
109.6
|
100
|
44.8
|
45(+0.5, -0)
|
45(+0.5, -0)
|
Above 60
|
Above 60
|
|
HY-72
|
72
|
72
|
77.4
|
62.5
|
67
|
67.5(+0.5, -0)
|
67.5(+0.5, -0)
|
Above 100
|
Above 83
|
|
HY-8000
|
96
|
96
|
77.4
|
62.5
|
91.6
|
92(+0.5, -0)
|
92(+0.5, -0)
|
Above 117
|
Above 117
|
|
HY-8200
|
96
|
96
|
75.1
|
62.5
|
91.6
|
92(+0.5, -0)
|
92(+0.5, -0)
|
Above 117
|
Above 117
|
|