- Simple temperature setting
- Clear digital indication
- ON/OF control, proportional control (changed by internal DIP switch)
- Space saving with the 62.5 mm short body length
Suffix codeDimensionRange and input code chartConnection diagramsTerminology & function explanation
The order from the left is the order in which the information is displayed at the bottom.
If you cancel the check, the information will be excluded, and if you check, it will be
printed out.
▍Specification
Input
Thermocouple input
TC-K
Reference junction
compensation accuracy
±1.5℃ (within -10 ~ 50 ℃)
RTD input
Pt 100 Ω
Allowable wiring resistance
10 Ω or less, but the resistance between 3 wires should be the same
Input sampling cycle
500 ms
Control
output
Output type
Relay : 1C, 250 V a.c. 5 A
Control type
ON/OFF control, Proportional control (Selective by Internal DIP switch)
Proportional band
1 ~ 10 ℃
Manual reset (MR)
0 ~ 100 %
Control cycle
20 sec
Hysteresis
2 ℃
Output acting
Reverse acting (heating)
Power
supply
Power supply voltage
100 - 240V a.c. 50 - 60 Hz
Voltage fluctuation rate
± 10 % of power supply voltage
Insulation Resistance
Min. 20 MΩ, 500 V d.c.
Dielectric strength
3,000 V a.c., 50/60 Hz for 1 minute (between 1st and 2nd terminal)