Specification
Input
Thermocouple input
K
RTD input
Pt 100 Ω
Input sampling cycle
500 ms
Input display resolution
1 ℃
Allowable
signal source resistance
Thermocouple max. 100 Ω
Lead wire allowable resistance
RTD (max. 10 Ω. but the resistance among 3 lines should be same)
Performance
Display accuracy
± 1 % of FS ± 1 Digit
Control
functions
and output
Control type
Proportional control
Control operation
Reverse action
Setting range
Same as range and input code
Proportional band
1 ~ 10 % of FS
Manual reset (MR)
-50 ~ +50 % (Output amount)
Proportional period
Approx. 20 sec (relay output)
Input disconnection detection
The output is OFF when the range is over 10 ℃
Control output
Contact capacity : 1 C, 250 V a.c. 3 A (resisitive load)