Model
|
LM1/3/6-DV
|
LM1/3/6-DA
|
LM1/3/6-AV
|
LM1/3/6-AA
|
|
Size
|
▪LM1 : 48(W) X 24(H) X 89(D) mm
▪LM3 : 96(W) x 48(H) x 68(D) mm
▪LM6 : 72(W) x 36(H) x 81(D) mm
|
|
Power
Supply Voltage
|
100 - 240 V a.c. 50/60 Hz (Voltage fluctuation rate : ±10%)
|
|
Power Consumption
|
▪LM1-N: Max. 4 VA ▪LM1-2R: Max. 5 VA
▪LM1-3N/3P: Max. 4 VA ▪LM1-RC: Max. 5 VA
▪LM1-RT: Max. 6 VA
▪LM3-N: 6 VA or less ▪LM3-3R/3RC: 10 VA or less
▪LM3-3RT: 11 VA or less ▪LM3-3NC/3PC: 9 VA or less
▪LM3-3NT/3PT: 10 VA or less
▪LM6-N: 5 VA or less ▪LM6-3R: 7 VA or less
▪LM6-3N/3P: 5 VA or less ▪LM6-RC: 6 VA or less
▪LM6-RT: 7 VA or less
|
|
Input signal
|
DC voltage
|
DC current
|
AC voltage / frequency
|
AC current / frequency
|
|
Input
range
|
LM1 |
50 V / 10 V
5 V / 1 V
200 mV / 50 mV
|
500 mA / 200 mA
50 mA / 4 - 20 mA
5 mA / 2 mA
|
250 V / 110 V
50 V / 20 V
5 V / 2 V
|
5 A / 2 A
500 mA / 200 mA
50 mA / 20 mA
|
LM3 |
500 V / 100 V
50 V / 10 V
5 V / 1 V
200 mV / 50 mV
|
5 A / 2 A
500 mA / 200 mA
50 mA / 4 - 20 mA
5 mA / 2 mA
|
500 V / 250 V
110 V / 50 V
20 V / 10 V
2 V / 1 V
|
5 A / 2 A
500 mA / 200 mA
50 mA / 20 mA
|
LM6 |
|
AC measurement method
|
AVG / RMS selective measurement
|
|
Input sampling cycle
|
50 ms
|
|
Input sampling method
|
OVER sampling method using continuous approximation A / D converter
|
|
Maximum allowable input
|
F.S. of each input range 110 %
|
|
Frequency measurement range
|
0.2 ~ 9999 Hz (Frequency measurement range depends on the decimal point position)
|
|
Display
|
▪Negative-LCD ▪4 digit 2 rows ▪PV (White) ▪SV (Green)
|
|
Character size
|
▪LM1 : 10.2 X 4.0 mm▪LM3 : 17.6 x 10.6 mm ▪LM6 : 7.0 x 11.5 mm
|
|
Maximum display
|
-9999 ~ 9999
|
|
Display degree
|
▪[ 23 ℃ ± 5 ℃ ] - F.S. ± 0.1 % rdg ± 2 digit
▪[ 23 ℃ ± 5 ℃, 5 A ] - F.S. ± 0.3 % rdg ± 3 digit
▪[ 50 ℃ ~ -10 ℃ ] - F.S. ± 0.5 % rdg ±3 digit
|
▪[ 23 ℃ ± 5 ℃ ] - F.S. ± 0.3 % rdg ±3 digit
▪[ 23 ℃ ± 5 ℃, frequency ] - F.S. ± 0.1 % rdg ± 2 digit
▪[ 50 ℃ ~ -10 ℃ ] - F.S. ± 0.5 % rdg ± 3 digit
|
|
Control output
|
▪Contact output : 3 stage, SPST (1a), 250 V a.c. 5 A
▪Solid state output: 3-stage, NPN or PNP open collector, 12 - 24 V d.c. 50mA or less
|
|
Relay
life
|
LM1 |
▪Electrical (about 50,000 times, 250 V a.c. 5 A)
▪Mechanical (about 20 million times)
|
|
LM3
LM6
|
▪Electrical (about 100,000 times, 250 V a.c. 5 A)
▪Mechanical (about 5 million times)
|
|
Optional
output
|
External
input
|
▪HOLD/ZERO Optional input ▪Non-voltage input ▪Short circuit impedance: 300 Ω or less
▪Residual voltage: 1 V or less ▪Impedance when open: 100 kΩ or more
|
|
4-20 mA
output
|
▪Resolution : 10,000 sections
▪Response speed : 450 ms or less
▪Load resistance : 600 Ω or less
|
|
Communication
|
▪Communication protocol : Modbus-RTU
▪Communication method : RS-485 (2-wire half duplex)
▪Communication speed : 2400 / 4800 / 9600 / 19200 / 38400 bps
|
|
Insulation Resistance
|
100 ㏁ or more (500 V d.c. Mega standard, between conductive terminal and case)
|
|
Withstand voltage
|
2000 V a.c. 60 Hz 1 minute (between conductive terminal and case)
|
|
Noise
|
± 2 kV(Between operation power terminals, Pulse width = 1 us, Square wave noise by noise simulator)
|
|
Vibration resistance
|
10 - 55 ㎐, Single amplitude 0.5 ㎜, 3 - axis angular, 2 hours
|
|
Certification
|
LM1 |
|
|
LM3
LM6
|
 |
|
Protection structure
|
▪IP66 (front) ▪Terminal block protection cover applied
|
|
Ambient temperature
and humidity
|
-10 ~ 50 ℃, 35 ~ 85 % R.H.
|
|
Storage temperature
|
-20 ~ 65 ℃
|