MC9 Digital temperature controller
- Digital Input (DI)
- Control 4/8 channels
- Communication function (RS232, RS485/422)
- Heating/cooling control (4 channels)
CE

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

■ Input specification

Title

Description

Temperature input

Thermocouple (T.C) : K, J, R, S, B, E, N, T, W, PL2, U, L

RTD (R.T.D) : Pt100 Ω, KPt100 Ω

Direct current voltage (DCV) : 0 ~ 5 V, 1 ~ 5 V, 0 ~ 10 V,4 ~ 20 ㎃

(250 Ω with external resistor)

The degree of display level

Thermocouple : ±(0.3 % of F.S ±1Digit) or ±2 °C, whichever is greater

RTD : (±0.3 % of F.S ±1Digit) or ±0.8 °C, whichever is greater

DC voltage : ±0.3 % of F.S ±1Digit

Sampling cycle

1 second

Input display resolution

Basically, below the decimal point of the "measurement range index"

Input impedance

1 ㏁ or more. (Input thermocouple and DC voltage)

Effect of allowable input resistance

about 0.2 ㎶/Ω

Acceptable input wire resistance

Temperature resistance

(10 Ω or less. However, the resistance between the three lines will be the same)

Acceptable input voltage

Within 2–5 V (thermal band, thermoelectric resistor), within -5–12 V (d. c. voltage)

Scaling

0.0 % ~ 100.0 % of F.S

Input correction

±100 % of F.S

Reference point

compensation error

±1.5 ℃ (Between 0 and 50°C)

Input open circuit detection

UP SCALE (reverse acting), DOWN SCALE (reverse acrion)

Insulation resistance

20 ㏁ or morte (500 V d.c.), Measurement terminal-Power terminal

Voltage resistance

2,300 V a.c. 50/60 ㎐, For a minute. Measurement terminal-Power terminal.

■ Output specification

Title

Description

Control output

Relay output

Contact capacities: 1a, 250Va.c., 3A. (resistance load)

Proportional cycle: 1 to 1,000 seconds

Time resolution: 0.1 % or 10 ms, whichever is smaller

S.S.R

(voltage pulse)

(voltage pulse) Voltage pulse : More than or equal to about 12 V d.c. (Load resistance of 600 or more)

Proportional cycle: 1 to 1,000 seconds

Time resolution: 0.1% or 10%, whichever is smaller

S.C.R

(Current.)

Current. : 4-20 ㎃ d.c., 0 ~ 20 ㎃ (Load resistance less than 600)

Degree : ±1.0 % of F.S (4-20 ㎃ range)

Alarm output

(Relay)

Temperature

alarm

(AL1,2,3)

1a, 250 V a.c., 1 A. 30 V d.c. 1 A (Resistance load)

Output score : Up to 3 points (depending on the selection specification)

Short-loop

warning

(L.B.A)

1a 1point, 250 V a.c., 1 A. 30 V d.c. 1A (Resistance load)

Proportional period : 1 ~ 1,000 seconds

■ General specification

Title

Description

Power supply voltage

100 - 240 V a.c., 50 / 60 ㎐

Voltage fluctuation rate

Power supply voltage ±10 %

Power consumption

21 VA

Ambient temperature

0 - 50 ℃

Ambient humidity

35 - 85 % RH (Without condensation)

Storage temperature

-25 ~ 65 ℃

Vibration resistance

10 - 55 ㎐, One-sided width 0.75 ㎜, Three axis, in each direction, 2h

Shock resistance

300 m/s², Three axis, in each direction. Three times each

Weight

700 g

■ Communication specification

Title

Description

Applied specification

EIA-RS485, RS422A

Maximum number

of connection

31 or 255 units

Communication method

2-wire half-duplex, or 4-wire half-duplex

Synchronous Way

Asynchronous

Communication order

No order

Communication distance

1.2 ㎞ max

Communication speed

1,200/2,400/4,800/9,600/19,200/38,400/57,600/76,800/115,200 bps (Change by parameter setting)

Start bit

1 Bit

Date bit

7 or 8 Bit

Parity bit

None, Even number, Odd number

Stom bit

1 or 2 Bit

Protocol

PC Link SUM none(0), PC Link SUM Have (1)

Modbus ASCII(2), Modbus RTU(3)

Response delay time

Receipt processing time + (response time X 10)