▍Specification
■ Input specification
|
Title
|
Description
|
|
Temperature input
|
Thermocouple (T.C) : K, J, R, S, B, E, N, T, W, PL2, U, L
RTD (R.T.D) : Pt100 Ω, KPt100 Ω
Direct current voltage (DCV) : 0 ~ 5 V, 1 ~ 5 V, 0 ~ 10 V,4 ~ 20 ㎃
(250 Ω with external resistor)
|
|
The degree of display level
|
Thermocouple : ±(0.3 % of F.S ±1Digit) or ±2 °C, whichever is greater
RTD : (±0.3 % of F.S ±1Digit) or ±0.8 °C, whichever is greater
DC voltage : ±0.3 % of F.S ±1Digit
|
|
Sampling cycle
|
1 second
|
|
Input display resolution
|
Basically, below the decimal point of the "measurement range index"
|
|
Input impedance
|
1 ㏁ or more. (Input thermocouple and DC voltage)
|
|
Effect of allowable input resistance
|
about 0.2 ㎶/Ω
|
|
Acceptable input wire resistance
|
Temperature resistance
(10 Ω or less. However, the resistance between the three lines will be the same)
|
|
Acceptable input voltage
|
Within 2–5 V (thermal band, thermoelectric resistor), within -5–12 V (d. c.
voltage)
|
|
Scaling
|
0.0 % ~ 100.0 % of F.S
|
|
Input correction
|
±100 % of F.S
|
|
Reference point
compensation error
|
±1.5 ℃ (Between 0 and 50°C)
|
|
Input open circuit detection
|
UP SCALE (reverse acting), DOWN SCALE (reverse acrion)
|
|
Insulation resistance
|
20 ㏁ or morte (500 V d.c.), Measurement terminal-Power terminal
|
|
Voltage resistance
|
2,300 V a.c. 50/60 ㎐, For a minute. Measurement terminal-Power terminal.
|
■ Output specification
|
Title
|
Description
|
|
Control output
|
Relay output
|
Contact capacities: 1a, 250Va.c., 3A. (resistance load)
Proportional cycle: 1 to 1,000 seconds
Time resolution: 0.1 % or 10 ms, whichever is smaller
|
|
S.S.R
(voltage pulse)
|
(voltage pulse) Voltage pulse : More than or equal to about 12 V d.c.
(Load resistance of 600 or more)
Proportional cycle: 1 to 1,000 seconds
Time resolution: 0.1% or 10%, whichever is smaller
|
|
S.C.R
(Current.)
|
Current. : 4-20 ㎃ d.c., 0 ~ 20 ㎃ (Load resistance less than 600)
Degree : ±1.0 % of F.S (4-20 ㎃ range)
|
|
Alarm output
(Relay)
|
Temperature
alarm
(AL1,2,3)
|
1a, 250 V a.c., 1 A. 30 V d.c. 1 A (Resistance load)
Output score : Up to 3 points (depending on the selection specification)
|
|
Short-loop
warning
(L.B.A)
|
1a 1point, 250 V a.c., 1 A. 30 V d.c. 1A (Resistance load)
Proportional period : 1 ~ 1,000 seconds
|
■ General specification
|
Title
|
Description
|
|
Power supply voltage
|
100 - 240 V a.c., 50 / 60 ㎐
|
|
Voltage fluctuation rate
|
Power supply voltage ±10 %
|
|
Power consumption
|
21 VA
|
|
Ambient temperature
|
0 - 50 ℃
|
|
Ambient humidity
|
35 - 85 % RH (Without condensation)
|
|
Storage temperature
|
-25 ~ 65 ℃
|
|
Vibration resistance
|
10 - 55 ㎐, One-sided width 0.75 ㎜, Three axis, in each direction, 2h
|
|
Shock resistance
|
300 m/s², Three axis, in each direction. Three times each
|
|
Weight
|
700 g
|
■ Communication specification
|
Title
|
Description
|
|
Applied specification
|
EIA-RS485, RS422A
|
|
Maximum number
of connection
|
31 or 255 units
|
|
Communication method
|
2-wire half-duplex, or 4-wire half-duplex
|
|
Synchronous Way
|
Asynchronous
|
|
Communication order
|
No order
|
|
Communication distance
|
1.2 ㎞ max
|
|
Communication speed
|
1,200/2,400/4,800/9,600/19,200/38,400/57,600/76,800/115,200 bps (Change by parameter setting)
|
|
Start bit
|
1 Bit
|
|
Date bit
|
7 or 8 Bit
|
|
Parity bit
|
None, Even number, Odd number
|
|
Stom bit
|
1 or 2 Bit
|
|
Protocol
|
PC Link SUM none(0), PC Link SUM Have (1)
Modbus ASCII(2), Modbus RTU(3)
|
|
Response delay time
|
Receipt processing time + (response time X 10)
|
|