Model
|
SM100-□A20
|
SM100-□A16
|
SM100-□A12
|
|
Control output channel
|
20 channel
|
16 channel
|
12 channel
|
|
Measurement input
|
Input type
|
Thermocouple (K), range : -199.9 ℃ ~ 999.9 ℃
RTD (Pt100 Ω), range : -199.9 ℃ ~ 640.0 ℃
|
|
Display accuracy
|
Maximum range ± 0.5 % (± 0.5 % of F.S)
|
|
R.J.C precision
|
Within display precision
|
|
Sampling frequency
|
1 second
|
|
Input calibration
|
-1200.0 ℃ to1200.0 ℃
|
|
Input filter
|
0.0 to 120.0 seconds
|
|
Burn-out action
|
Thermocouple : Upscale
RTD : Upscale
|
|
Setting and
display
|
Setup method
|
Setup using acommunication program
|
|
Number of setting
|
20 points
|
16 points
|
12 points
|
|
Memory Storage
|
Storage using semiconductors
|
|
Device address settings
|
Setup using the built-in HEX BCD switch (1 to 15)
|
|
Display LEDs
|
Power display, communication display, control output display
|
|
Control
output
|
Output type
|
Voltage pulse output for SSR drive
(drive voltage : 12 V d.c., load resistance of 600 Ω or more)
|
|
Control action
|
Time division proportion PID or ON/OFF control
|
|
Number ofPID groups
|
1 group / channel
|
|
Proportional cycle
(output cycle)
|
1 to 100 seconds
|
|
Proportional band (P)
|
0 to 1200.0 ℃
|
|
Integral time (I)
|
1 to 3600 seconds
|
|
Derivative time (D)
|
1 to 3600 seconds
|
|
Anti-Reset Windup(A.R.W)
|
0.1 to 100.0 % ※ “0” setting (Auto)
|
|
Manual reset
|
0.0 to 100.0 % (with ON/OFF control)
|
|
Hysteresis
|
0 to 120.0 ℃ (with ON/OFF control))
|
|
Control output action
|
Select cooling control (Direct action) /
heating control (reverse action)
|
|
Emergency output
|
0.0 to 100.0 %
|
|
Event output
|
Number of output points
|
1a 3 points (AL1, AL2, AL3)
|
|
Control action types
|
1a 3 points (AL1, AL2, AL3)
|
|
Loop burnout alarm
|
0 to 7200 seconds (OFF when set to "0")
|
|
Hysteresis
|
0 ℃ to 120.0 ℃
|
|
Output action
|
ON/OFF action
|
|
Output type
|
Relay output
|
|
Contact capacity
|
5 A 250 V a.c. (5 A 30 V d.c.)
|
|
Digital input
|
Number of external contact inputs
|
1 point (RUN / STOP according to the built-in dip switch)
|
|
Communication
specifi cation
|
RS485/ 422
|
Communication standards
|
ELA-RS485/422(4-Wire type)
|
|
Communication method
|
Half duplex
|
|
Maximum number of connections
|
15 units ※ Address setting method using the HEX BCD switch
|
|
Communication sequence
|
No sequence
|
|
Start bit
|
1 Bit
|
|
Stop bit
|
1 Bit
|
|
Parity bit
|
Even
|
|
Data length
|
8 Bit
|
|
Transmission speed
|
19200 bps
|
|
Communication distance
|
1.2 ㎞ MAX
|
|
Communication protocol
|
PC Link with SUM
|
|
Response time
|
Receiving processing time + (response set time x 25 ㎳)
|
|
General specification
|
Power voltage
|
100 V - 240 V a.c. 50/60 Hz
|
|
Power supply voltage fluctuation rate
|
±10% of rated power voltage
|
|
Power consumption
|
25 VA MAX.
|
|
Insulation resistance
|
20 MΩ Min. Power and ground terminals (500 V d.c. in megaohms)
|
|
Dielectric strength
|
2,000 V a.c. for 1 minute; power and ground terminals
|
|
Ambient temperature
|
0 to 50 ℃
|
|
Ambient humidity
|
50 to 85 % RH (however, there should be no condensation)
|
|
Storage temperature
|
-20 to 70 ℃ (however, there should be no condensation)
|
|
Vibration (durabilit)
|
10 Hz ~ 55 Hz 19.6 m/s² 3 axis 6 directions 2 h
|
|
Shock (durabilit)
|
196 m/s², 3 times in each of 6 directions of 3 axes
|
|
Case material
|
Cold rolled steel plate (SPC)
|
|
Installation
|
Fasten using screws
|
|
Certification
|
|
|
Weight
|
Approximately 1,000g
|