SM100 Board type multi channel Temperature controller
- Cooling control and heating control selection
- Alarm output and timer output selection
- ON / OFF and proportional control selection
- 0.1 ℃ / 1 ℃ selection
- Delay output time setting
CE

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍ Specification

Model

SM100-□A20

SM100-□A16

SM100-□A12

Control output channel

20 channel

16 channel

12 channel

Measurement input

Input type

Thermocouple (K), range : -199.9 ℃ ~ 999.9 ℃

RTD (Pt100 Ω), range : -199.9 ℃ ~ 640.0 ℃

Display accuracy

Maximum range ± 0.5 % (± 0.5 % of F.S)

R.J.C precision

Within display precision

Sampling frequency

1 second

Input calibration

-1200.0 ℃ to1200.0 ℃

Input filter

0.0 to 120.0 seconds

Burn-out action

Thermocouple : Upscale

RTD : Upscale

Setting and

display

Setup method

Setup using acommunication program

Number of setting

20 points

16 points

12 points

Memory Storage

Storage using semiconductors

Device address settings

Setup using the built-in HEX BCD switch (1 to 15)

Display LEDs

Power display, communication display, control output display

Control

output

Output type

Voltage pulse output for SSR drive

(drive voltage : 12 V d.c., load resistance of 600 Ω or more)

Control action

Time division proportion PID or ON/OFF control

Number ofPID groups

1 group / channel

Proportional cycle

(output cycle)

1 to 100 seconds

Proportional band (P)

0 to 1200.0 ℃

Integral time (I)

1 to 3600 seconds

Derivative time (D)

1 to 3600 seconds

Anti-Reset Windup(A.R.W)

0.1 to 100.0 % ※ “0” setting (Auto)

Manual reset

0.0 to 100.0 % (with ON/OFF control)

Hysteresis

0 to 120.0 ℃ (with ON/OFF control))

Control output action

Select cooling control (Direct action) /

heating control (reverse action)

Emergency output

0.0 to 100.0 %

Event output

Number of output points

1a 3 points (AL1, AL2, AL3)

Control action types

1a 3 points (AL1, AL2, AL3)

Loop burnout alarm

0 to 7200 seconds (OFF when set to "0")

Hysteresis

0 ℃ to 120.0 ℃

Output action

ON/OFF action

Output type

Relay output

Contact capacity

5 A 250 V a.c. (5 A 30 V d.c.)

Digital input

Number of external contact inputs

1 point (RUN / STOP according to the built-in dip switch)

Communication

specifi cation

RS485/ 422

Communication standards

ELA-RS485/422(4-Wire type)

Communication method

Half duplex

Maximum number of connections

15 units ※ Address setting method using the HEX BCD switch

Communication sequence

No sequence

Start bit

1 Bit

Stop bit

1 Bit

Parity bit

Even

Data length

8 Bit

Transmission speed

19200 bps

Communication distance

1.2 ㎞ MAX

Communication protocol

PC Link with SUM

Response time

Receiving processing time + (response set time x 25 ㎳)

General specification

Power voltage

100 V - 240 V a.c. 50/60 Hz

Power supply voltage fluctuation rate

±10% of rated power voltage

Power consumption

25 VA MAX.

Insulation resistance

20 MΩ Min. Power and ground terminals (500 V d.c. in megaohms)

Dielectric strength

2,000 V a.c. for 1 minute; power and ground terminals

Ambient temperature

0 to 50 ℃

Ambient humidity

50 to 85 % RH (however, there should be no condensation)

Storage temperature

-20 to 70 ℃ (however, there should be no condensation)

Vibration (durabilit)

10 Hz ~ 55 Hz 19.6 m/s² 3 axis 6 directions 2 h

Shock (durabilit)

196 m/s², 3 times in each of 6 directions of 3 axes

Case material

Cold rolled steel plate (SPC)

Installation

Fasten using screws

Certification

CE

Weight

Approximately 1,000g