BX8 Board type digital temperature controller
- PID auto tuning
- Multi inputs (various sensor inputs)

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

■ Input

Input

Thermocouple: K, J, E, T, R, B, S, L, N, U, WRe 5-26, PL-Ⅱ

RTD : Pt100 Ω, KPt100 Ω.

Direct voltage : 1 - 5 V, -10 - 20 ㎷, 0 - 100 ㎷ (free scale)

Sampling cycle

250 ㎳

Input resolution

Below decimal point of measurement range

Input impedance

Thermocouple and mV input: min. 1 ㏁, DC V: 1 ㏁

Allowable signal source resistance

Thermocouple : max. 250 Ω, Voltage : max. 2 kΩ

Lead wire tolerable resistance

RTD: max. 10 Ω / 1 wire

(but the conductor resistance among 3 wires should be the same)

Input tolerable voltage

within ±10 V (T/C, RTD, Voltage : mV DC), ±20 V (Voltage : VDC)

Noise removal rate

NMRR (Normal mode) : min. 40 dB (50/60 ㎐ ±1 %)

CMRR (Common mode) : min. 120 dB (50/60 ㎐ ±1 %)

Standard

T/C, RTD : KS, IEC, DIN

Standard junction temp.

compensation toleranc

±1.5 ℃ (15 ~ 35 ℃), ±2.0 ℃ (0 ~ 50 ℃)

BURN-OUT

T/C: OFF, UP/DOWN scale selectable. RTD : UP Scale

(detection current at thermocouple and RTD BURN-OUT: approx. 50 nA)

Accuracy

±0.5 % (FULL SCALE)

Input range

T/C and RTD are changeable within range of input signal and measurement range.

DC voltage: min. voltage and max. voltage are changeable within each measurement range.

Scaling available in the measurement range conditions

■ Output

Retransmission output

▪ Resolution : Approx. 3,000

▪ Sampling cycle : 250 ㎳

▪ Accuracy : ±0.5 % of max. scale (4 - 20 ㎃ range)

Alarm output

▪ Contact: 1a

▪ Point: 1 point

▪ Output points: Refer to “Terminal Arrangement”

Control

output

Relay contact

output

▪ Time resolution : 0.1 % or 10 ms (the smaller)

▪ Proportional cycle : 1 ~ 1000 sec.

▪ Output operation : time proportional, ON/OFF

▪ Output limit : 0.0~100.0 % range, high limit(OH) or low limit(OL) (selectable also during AT)

▪ ON/OFF hysteresis : 0 ~ 100 % (Full scale)

SSR

voltage pulse

output

▪ Proportional cycle: 1 ~ 1,000 sec

▪ OFF voltage: max. 0.1 V d.c.

▪ Output operation: time proportional

▪ Output limit: 0.0~100.0 % range, high limit (OH) low limit(OL) (selectable also during AT)

Current

output

(4-20 mA)

▪ Sampling time : 250 ms

▪ Output operation : PID control

▪ Accuracy : ±0.5 % of full scale (4 - 20 mA range), Resolution : Approx. 3,000l

▪ Output ripple : max. 0.3 % (P-P) of max. scale (150 Hz)

▪ Output limit : -5.0 ~ 105.0 % range, high limit(OH) or low limit(OL) (selectable also during AT)

※ Output type can be selected from relay, current or SSR and heating/cooling types can be set individually

▍Suffix code

Model

Code

Information

BX8-

48x48 ㎜ Board Type Digital Temperature Controller

Control Type

0

 

Normal Type

1

 

Heating / Cooling

Optional

0

SV2 / SV3

1

HBA

2

RS485

3

HBA / RS485

▍Dimension & Panel cutout

■ Display

표시부

※ Cable length basically 300 ㎜

■ Control

제어부