The order from the left is the order in which the information is displayed at the bottom.
If you cancel the check, the information will be excluded, and if you check, it will be
printed out.
▍Specification
■ Input
Input
Thermocouple: K, J, E, T, R, B, S, L, N, U, WRe 5-26, PL-Ⅱ
RTD : Pt100 Ω, KPt100 Ω.
Direct voltage : 1 - 5 V, -10 - 20 ㎷, 0 - 100 ㎷ (free scale)
Sampling cycle
250 ㎳
Input resolution
Below decimal point of measurement range
Input impedance
Thermocouple and mV input: min. 1 ㏁, DC V: 1 ㏁
Allowable signal source resistance
Thermocouple : max. 250 Ω, Voltage : max. 2 kΩ
Lead wire tolerable resistance
RTD: max. 10 Ω / 1 wire
(but the conductor resistance among 3 wires should be the same)
Input tolerable voltage
within ±10 V (T/C, RTD, Voltage : mV DC), ±20 V (Voltage : VDC)
Noise removal rate
NMRR (Normal mode) : min. 40 dB (50/60 ㎐ ±1 %)
CMRR (Common mode) : min. 120 dB (50/60 ㎐ ±1 %)
Standard
T/C, RTD : KS, IEC, DIN
Standard junction temp.
compensation toleranc
±1.5 ℃ (15 ~ 35 ℃), ±2.0 ℃ (0 ~ 50 ℃)
BURN-OUT
T/C: OFF, UP/DOWN scale selectable. RTD : UP Scale
(detection current at thermocouple and RTD BURN-OUT: approx. 50 nA)
Accuracy
±0.5 % (FULL SCALE)
Input range
T/C and RTD are changeable within range of input signal and measurement range.
DC voltage: min. voltage and max. voltage are changeable within each measurement range.
Scaling available in the measurement range conditions