▍Specification
|
Classification
|
AX2
|
AX3
|
AX4
|
AX7
|
AX9
|
|
Input
|
Thermocouple
|
K, J, R, T (selection by internal parameter)
|
|
RTD
|
Pt100 Ω (selection by internal parameter)
|
|
Allowable line resistance
|
Max. 10 Ω/1 wire (RTD).
Resistances among 3 wires should be same
|
|
Sampling cycle
|
0.1 sec
|
|
Impedance
|
Max. 1 ㏁
|
|
Input voltage
|
Max. 10 V d.c.
|
|
Display accuracy
|
±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range)
|
|
Control
output
|
Relay output
|
• 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load)
• You can select max. 3 relay outputs, and relay control output is output as RLY1.
2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among
RLY1, RLY2, RLY3.
|
|
SSR
output
|
Time share cycle control (CYC)
|
12 - 15 V d.c. pulse voltage (resistive load min. 600 Ω)
|
|
Phase control (PHA)
|
|
Current output (SCR)
|
4 - 20 ㎃ d.c. (resistive load max. 600 Ω)
|
|
Control
|
Control type
|
PID control (by auto-tuning), P control, ON/OFF control
|
|
Auto-tuning
|
PID operation by auto-tuning
|
|
ON/OFF control
|
When PV > SV, 0% output. When PV < SV, 100% output (only when control hysteresis is 0)
|
|
Manual reset
|
User set within 0.0% to 100.0% range
|
|
Control output operation
|
Direct/reverse actions ※ selection by parameter setting
|
|
Control output
|
Relay/voltage pulse (SSR) outputs ※ selection by parameter setting
|
|
Power
|
Power voltage
|
100 - 240 V a.c., 50/60 Hz
|
|
Voltage fluctuation rate
|
±10 % of power voltage
|
|
Insulation resistance
|
Min. 20 ㏁, 500 V d.c. for 1 min (primary terminal - secondary terminal)
|
|
Dielectric strength
|
2,300 V a.c. 50/60Hz, for 1 min (primary terminal - secondary terminal)
|
|
Power consumption
|
Max. 5.5 VA
|
|
Ambient
temperature & humidity
|
-5 ~ 50 ℃, 35 ~ 85 % RH (without condensation)
|
|
Vibration resistance
|
10 - 55 Hz, single amplitude 0.75 mm, 2 hours in each of 3 axis directions
|
|
Shock resistance
|
300 m/s² to 3 directions each 3 times
|
|
Approval
|
|
|
Weight
|
320g
|
320g
|
180g
|
300g
|
400g
|
▍Suffix code
|
Model
|
Code
|
Content
|
| AX |
-
|
|
|
Universal Input Digital Temperature Controller
|
|
Size
|
2
|
|
|
48(W) x 96(H) x 63(D) ㎜
|
|
3
|
|
|
96(W) x 48(H) x 63(D) ㎜
|
|
4
|
|
|
48(W) x 48(H) x 63(D) ㎜
|
|
7
|
|
|
72(W) x 72(H) x 63(D) ㎜
|
| 9 |
|
|
96(W) x 96(H) x 63(D) ㎜
|
|
Output
selection
|
1
|
|
SSR + Relay1 + Relay2
|
When using relay or SSR output
(selection by internal parameter)
|
|
2
|
|
SSR + Relay1 + Relay2 + Relay3
|
|
1B
|
|
SSR + Relay1(Form c) + Relay2
|
Only for AX2, 3, 7, 9
|
|
2B
|
|
SSR + Relay1(Form c) + Relay2 + Relay3
|
|
3
|
|
4 - 20 ㎃ + Relay2
|
When using current output
|
|
4
|
|
4 - 20 ㎃ + Relay2 + Relay3
|
|
Power voltage
|
A
|
100 - 240 V a.c. 50/60 Hz
|
- Relay output operates as control output, alarm output and LBA output according to internal parameter setting.
▍Dimension and panel cutout
■ Dimension
|
Classification
|
Type
|
AX2
|
AX3
|
AX4
|
AX7
|
AX9
|
|
Product
dimensions
|
W
|
48.0
|
96.0
|
48.0
|
72.0
|
96.0
|
|
H
|
96.0
|
48.0
|
48.0
|
72.0
|
96.0
|
|
D
|
63.0
|
63.0
|
63.0
|
63.0
|
63.0
|
|
D1
|
5.5
|
5.5
|
5.5
|
5.5
|
5.5
|
■ Panel cutout
|
Classification
|
Type
|
AX2
|
AX3
|
AX4
|
AX7
|
AX9
|
|
Panel
cutout
|
W1 *
|
45.0
|
92.0
|
45.0
|
68.0
|
92.0
|
| H1 * |
92.0 |
45.0 |
45.0 |
68.0 |
92.0 |
| A |
70.0
|
122.0
|
60.0
|
83.0
|
117.0
|
|
B
|
122.0
|
70.0
|
60.0
|
100.0
|
117.0
|
|
* +0.5 mm tolerance applied
|
■ Bracket assembling
■ Case disassembling
|