T38A Analog small timer
- 38.4(W) × 42.4(H) ×59.0(D) mm Compact size
- Easy time setting by using the dial
- Multi-time Range : 18 Multiple time Range
- Various output operations : 6 operating modes
- Various time setting range : 0.1sec ~ 60 hour
- Selecting units of time (sec, min, hour)
- Easy maintenance by installing the flush mounting type bracket
- 24 - 240 V a.c. 50/60 Hz, 24 - 240 V d.c. dual usage
CE

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

Model

T38A

Timer type

Analog small timer

Power supply voltage

24 - 240 V a.c. 50/60 Hz or 24 - 240 V d.c. dual usage

Allowable voltage

±10 % of Power supply voltage

Power consumption

▪Max. 4.1 VA (24 – 240 V a.c. 50/60 Hz)  ▪Max. 2 W (24 – 240 V d.c.)

Operating time range

0.1 sec ~ 60 hour

Operating time error

▪Setting error: Max. ±5 % ±0.05    ▪Repetition error: Max. ±0.3 % (※ percentage of full scale)

▪Voltage error: Max. ±0.5 %   ▪Temperature error: Max. ±2 %

Return time

Max. 100 ms

External connection method

8-pin socket

Control

output

Operation mode

A/B/C/D/E/F (selected by front operating mode selector switch)

Contact composition

▪instantaneous SPDT (1c) + time-limit SPDT (1c)

▪time-limit DPDT (2c) * Automatic change of contact composition according to operation mode

Contact capacity

▪N.O. (250 V a.c. 3A Resistive load)

▪N.C. (250 V a.c. 2A Resistive load)

Relay life

▪Mechanical life : Min 10 million cycles

▪Electrical life : Min. 20,000 cycles (250 V a.c. 2 A resistive load)

Insulation resistance

Min. 100 MΩ (500 V d.c. mega, at conductive terminal and non-charged metal which is exposed)

Dielectric strength

2000 V a.c. 60 Hz for 1 minute (conductive terminal and non-charged metal which is exposed)

Noise immunity

±2kV (between the power terminals, pulse width = 1 us, square wave noise by noise simulator)

Vibration resistance

10 - 55 Hz (for 1 minute) double amplitude 0.75 mm in each X · Y · Z direction for 2 hours

Shock resistance

300 m/s² (30G) in each X, Y, Z direction for 3 times

Operating ambient temperature

-10 ~ 55 ℃ (without condensation)

Accessories

▪Fixing BRACKET    ▪BRACKET-M (48.0 X 59.0 mm) flush type bracket

Accessories (separately sold)

▪BRACKET-S (48.0 X 48.0 mm) bracket for adjusting size (flush type)

▪BRACKET-L (53.5 X 84.4 mm) bracket for adjusting size (flush type)

Weight

Approx. 74 g (exposure type)

Approval

CE