▍Specification
■ Input
Input |
R.T.D
| R.T.D (Resistance Temperature Detector) : Pt 100 Ω IEC751 |
VDC |
0 - 5 V d.c
※ In case of using Digital Temperature Sensor (Example : EE99), please connect resistance 250 Ω in parallel on the exterior
|
Sampling cycle |
125 ms |
| Measurable range
| Temperature |
-100.0 ~ 200.0 °C |
Humidity |
0.0 ~ 100.0 % R.H |
| Accuracy |
Temperature
| ± 0.1 % of F.S |
Humidity |
± 2 % of F.S |
Contact Input (D.I) |
8 points (1a 8 points, 2 COM) |
■ Output
Control Output |
S.S.R |
▪ON : 24 V d.c., ▪OFF : Less than 0.1 V d.c.
▪Pulse voltage (More than load resistance 800 Ω)
|
Cycle time : 1 ~ 1,000 sec |
Current Output (S.C.R) |
4 - 20 mA d.c. (1 V - 5 V)
※ Load resistance : Less than 600 Ω
|
|
Retransmission
Output
|
Temperature |
4 - 20 mA d.c. (Load resistance : Less than 600 Ω)
PV / MV / SV(Internal selection)
|
Humidity |
Resolution |
Around 8,000 (4 - 20 mA) |
Renewal Time |
500 ms |
Digital Output (D.O) |
Relay |
12 points(1c 4 points, 1a 8 points) |
|
▪N.0 : 30 V d.c., 5A, 250 V a.c. : 5A
▪N.C : 30 V d.c., 1A, 250 V a.c. : 2A
|
Transistor |
8 points (2 COM) |
24 V d.c. 300 mA Max. (Open Collector) |
■ Communication
Applicable standard |
▪E1A-RS232C ▪RS485/422 ▪USB V2.0 |
max connection |
RS232C |
1 : 1 |
RS485/422 |
max 32 devices (master included) ※ address : 1 ~ 999 |
Communication type |
RS232C |
Full duplex |
RS485/422 |
2 wire type, 4 wire type : Half-duplex |
Synchronizing system |
RS232, 485/422 |
asynchronous type |
Communication distance |
USB V1.1 |
approx. within 1 m |
RS232C |
approx. within 10 m |
RS485/422 |
approx. within 1.2 km |
Communication speed |
USB V1.1 |
approx. 1 M bps |
RS232, 485/422 |
9600 / 19200 / 38400 / 57600 / 115200 bps |
Data length |
RS232, 485/422 |
7 / 8 bits |
Parity bit |
RS232, 485/422 |
NONE / EVEN / ODD |
Stop bit |
RS232, 485/422 |
1 / 2 bit(s) |
Protocol |
USB V1.1 |
Bulk Mode |
RS232, 485/422 |
PCLINK / PCLINK+CRC / MODBUS - RTU |
Response delay time |
RS232, 485/422 |
0 - 999 ms |
■ Power Supply
Power supply voltage |
100 - 240 V a.c. (Change rate of voltage ± 10 %) |
Frequency |
50 - 60 Hz |
Power consumption |
20 VA max |
Insulation Resistance |
More than 500 V d.c. 20 MΩ Power supply terminal - exterior case, Input terminal - exterior case |
| Dielectric Strength |
2500 V a.c. 50 - 60 Hz : Power supply terminal - exterior case(F/G : Frame Ground),
Input terminal - exterior case (F/G : Frame Ground), Input terminal - Input terminal
|
External power supply |
24 V d.c 18 W max.(I/O Board) |
■ Functions
Input |
Bias
(Deviation)
|
Temp : -100.00 ~ 100.00 °C
Humidity : -100.0 ~ 100.0 % R.H
|
|
Dry· Wet
sensor Bias
|
After removing gauze from wet sensor, correct the difference between dry and wet sensor. |
Scaling |
V d.c. : Input scale in accordance with conversion range |
LPF |
2 ~ 180 sec |
|
Detection of
sensor
disconnection
|
Up scale (In case of R.T.D input),
Stop operation when it is over ± 5 % of its range
|
Control mode |
Operation
method
selection
|
Fix Control / Program Control |
Control output |
Temperature |
SSR / SCR (4 - 20 mA d.c.) |
Humidity
| SSR / SCR (4 - 20 mA d.c.) |
Control Action |
Pattern |
100 patterns (1 pattern / 100 segments) |
Segment |
6,000 max segments |
P.I.D group |
16 Groups (Temp 4 zones x Humidity 4 zones) |
Auto Tuning |
Auto Tuning according to SV (Setting Value) |
|
Proportional
Band
|
0.00 ~ 100.00 %
0.00 % = ON/OFF control
|
Integral Time |
0.0 ~ 6.000 sec ( 0 sec = OFF ) |
Derivative Time
| 0.0 ~ 6.000 sec ( 0 sec = OFF ) |
ON/OFF control |
Set the Proportional Band as 0.0 |
|
Direct/
Reverse action
|
Select Direct or Reverse action in control output. |
|
ON/OFF
Hysteresis
|
0 .1 ~ 300 ℃ |
In case of humidity, it is a web bulb temperature or converted value |
|
Retransmission
Output
|
TempㆍHumidity |
4 - 20 mA d.c., Select among PV, SV and MV (Manipulated Value) |
Scaling |
Perform scaling of the High· Low deviation range 4 - 20 mA d.c. automatically |
Alarm Setting |
Setting Alarm |
System Alarm : 4 points, Alarm per pattern : 4 points |
Alarm type |
Including High-Low / Low deviation alarm etc. 20 types of alarm are available. |
Process Alarm |
Temp : -100.0 ~ 200.0 °C |
Humidity : 0.0 ~ 100.0 % RH |
Deviation Alarm |
Temp : -300.0 ~ 300.0 °C |
Humidity : 0.0 ~ 100.0 % RH |
Hysteresis |
Temperature : 0.0 ~ 300.0 °C |
Humidity : 0.0 ~ 100.0 % RH |
|
Storage
against Power
failure
|
Memory |
Internal Flash Memory and FRAM |
Memory function |
Program Information and SV(Setting Value) backup and restoration.
Storage of Temperature-Humidity setting value and PV
|
■ Touch LCD
Standard |
TFT LCD 5.6” |
Resolution |
640 x RGB x 480 |
|
Life span
of back light
|
LED Back light (Approx. 40,000 hrs) |
Touch type |
Resistive Operation (4 Wires) |
Language |
▪Korean / English ▪English/Chinese (Simple) ▪English/Chinese (Traditional) |
■ Operation Environment
|
Usable
surrounding temperature
|
0 ~ 50 °C |
|
Usable
surrounding humidity
|
20 ~ 90 % RH (No condensation) |
Storage Temperature |
-25 °C ~ 70 °C |
Vibration |
10-55 Hz, amplitude : 0.75 mm, 3 directions 4 times, 5 min / cycle |
Shock |
147 m/s², 3 directions 3 times |
Dimension |
183 (W) x 144 (H) x 94 (D) |
Certification |
 |
Weight |
Approx. 2.35 Kg (Including packing materials) |
|