BK6-M Digital temperature indicator
- User input selection
- Transmission output
- Transmission output scale

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

model

Information

Power voltage

100 - 240 V a.c. 50 / 60 Hz

Allowable voltage fluctuation range

±10 % of proper voltage

Power consumption

Max. 4 VA

Input sensor

Thermocouple, RTD (please refer to the suffix code and range)

Send Output

4 - 20 mA ±0.5 % of FS ±1 digit

Indication type

7 segment red LED, height 14.2 mm

Indication accuracy

±0.5 % of F.S ±1 digit

Vibration Malfunction

Vibration Durability

10 - 50 Hz, Peak amplitude, X, Y, Z each direction for 10 minutes.

10 - 50 Hz, Peak amplitude, X, Y, Z each direction for 2 hours.

Shock Malfunction

Shock Durability

100 m/s² (Approx. 10G), X, Y, Z each direction 3 times each

300 m/s² (Approx. 30G), X, Y, Z each direction 3 times each

Burnout circuit

Indicate the max temperature when input circuit is disconnected (break)

External input resistance

Thermocouple-max reciprocale 100Ω, RTD: max 10Ω per 1 wire (but resistance value of each wire must be same)

Dielectric strength

2000 V a.c. 50/60 Hz for 1 minute.

Insulation resistance

Min 100 ㏁ (base on 500 V d.c. mega)

Ambient temperature / humidity

0 ~ 50 °C, 35 ~ 85 % R.H. (Without dew condensation)

Storage temperature

-20 ~ 70 °C (Without dew condensation)

Weight

120 g