▍Specification
■ Input
|
Model
|
TH300
|
|
Input
|
R.T.D
|
R.T.D (Resistance Temperature Detector) : (Pt100 Ω IEC751)
|
|
VDC
|
0 - 5 V d.c. ※ In case of using Digital Temperature Sensor (Example:EE99),
please connect resistance 250 Ω in parallel on the exterior
|
|
Sampling cycle
|
500 ms
|
|
Measurable range
|
Temperature
|
-100.0 ~ 500.0 ℃
|
|
Humidity
|
0.0 ~ 100.0 % R.H.
|
|
Accuracy
|
Temperature
|
± 0.2 % of F.S
|
|
Humidity
|
± 2 % of F.S
|
|
Contact Input (D.I)
|
4 points (1a 4 points, 1 COM)
|
■ Output
|
Model
|
TH300
|
|
Control Output
|
S.S.R
|
ON : 24 V d.c., OFF : Less than 0.1 V d.c.
Pulse voltage (More than load resistance 800 Ω)
|
|
Cycle time : 1 ~ 1,000 sec
|
|
Current Output
(S.C.R)
|
S.C.R is not available
|
|
Retransmission Output
|
Temperature
|
4 - 20 mA d.c. (Load resistance : Less than 600 Ω)
PV / MV / SV (Internal selection)
|
|
Humidity
|
|
Resolution
|
Around 7,000 (4 mA - 20 mA)
|
|
Renewal Time
|
500 ms
|
|
Digital Output
(D.O)
|
Relay
|
8 points (1a 8 points)
|
|
N.O : 30 V d.c., 5 A, 250 V a.c. : 5 A
N.C : 30 V d.c., 1 A, 250 V a.c. : 2 A
|
|
Transistor
|
4 points (1 COM)
|
|
24 V d.c. 300 mA max (Open Collector)
|
■ Communication
|
Model
|
TH300
|
|
Applicable standard
|
EIA-RS232C, RS485/422
|
|
max connection
|
RS232C
|
1 : 1
|
|
RS485 / 422
|
max 32 devices (master included) ※ address : 1 ~ 999
|
|
Communication type
|
RS232C
|
Full duplex
|
|
RS485 / 422
|
2 wire type, Half-duplex
|
|
Synchronizing system
|
RS232, 485/422
|
asynchronous type
|
|
Communication distance
|
RS232C
|
approx. within 10 m
|
|
RS485/422
|
approx. within 1.2 km
|
|
Communication speed
|
RS232, 485/422
|
9600/19200/38400 bps
|
|
Data length
|
RS232, 485/422
|
7 / 8 bits
|
|
Parity bit
|
RS232, 485/422
|
NONE / EVEN / ODD
|
|
Stop bit
|
RS232, 485/422
|
1 / 2 bit(s)
|
|
Protocol
|
RS232, 485/422
|
PC LINK / PC LINK + CRC / MODBUS - RTU
|
|
Response delay time
|
RS232, 485/422
|
0 - 999 ms
|
■ Power Supply
|
Model
|
TH300
|
|
Power supply voltage
|
100 - 240 V a.c. (Change rate of voltage : ± 10 %)
|
|
Frequency
|
50 - 60 Hz
|
|
Power consumption
|
10 VA max
|
|
Insulation Resistance
|
More than 500 V d.c. 10 MΩ
Power supply terminal - exterior box, Input terminal - exterior box
|
|
Dielectric Strength
|
2500 V a.c. 50 - 60 Hz : Power supply terminal - exterior case (F/G : Frame Ground),
Input terminal - exterior case (F/G : Frame Ground), Input terminal - Input terminal
|
|
External power supply
|
Not applied
|
■ Functions
|
Model
|
TH300
|
|
Input
|
Bias(Deviation)
|
Temp : -100.00 ~ 100.00 (℃)
Humidity : -100.0 ~ 100.0 (% R.H.)
|
|
Dry·Wet sensor Bias
|
After removing gauze from wet sensor, correct the difference between dry and wet sensor.
|
|
Scaling
|
V d.c. : Input scale in accordance with conversion range
|
|
LPF
|
1 ~ 180 sec
|
|
Detection of sensor disconnection
|
Up scale (In case of R.T.D input),
Stop operation when it is over ± 5 % of its range
|
|
Control mode
|
Operation method selection
|
Fix Control / Program Control
|
|
Control output
|
Temperature
|
SSR (Pulse Voltage)
|
|
Humidity
|
SSR (Pulse Voltage)
|
|
Control Action
|
Pattern
|
100 patterns (1 pattern/100 segments)
|
|
Segment
|
6,000 max segments
|
|
P.I.D group
|
16 Groups (Temp 4 zones x Humidity 4 zones)
|
|
Auto Tuning
|
Auto Tuning according to SV (Setting Value)
|
|
Proportional Band
|
Temp : 0.00 ~ 600.00 ℃
Humidity : 0.00 ~ 200.00 %
0.00 % = ON/OFF control
|
|
Integral Time
|
0.0 ~ 6.000 sec (0 sec = OFF)
|
|
Derivative Time
|
0.0 ~ 6.000 sec (0 sec = OFF)
|
|
ON/OFF control
|
Set the Proportional Band as 0.0
|
|
Direct/Reverse action
|
Select Direct or Reverse action in control output.
|
|
ON/OFF Hysteresis
|
0.1 ~ 600.0 ℃
|
|
(In case of humidity, it is a web bulb temperature or converted value)
|
|
Retransmission Output
|
TempㆍHumidity
|
4 - 20 mA d.c., Select among PV,SV and MV (Manipulated Value)
|
|
Scaling
|
Perform scaling of the High·Low deviation range 4 - 20 mA d.c. automatically
|
|
Alarm Setting
|
Setting Alarm
|
ㆍSystem Alarm : 4 points ㆍAlarm per pattern : 4 points
|
|
Alarm type
|
Including High Low / Low deviation alarm etc. 20 types of alarm are available.
|
|
Process Alarm
|
Temp. : -100.0 ~ 500.0 ℃
|
|
Humidity : 0.0 ~ 100.0 % RH
|
|
Deviation Alarm
|
Temp. : -600.0 ~ 600.0 ℃
|
|
Humidity : 0.0 ~ 100.0 % RH
|
|
Hysteresis
|
Temp. : 0.0 ~ 600.0 ℃
|
|
Humidity : 0.0 ~ 100.0 % RH
|
|
Storage against Power failure
|
Memory
|
Internal Flash Memory and FRAM
|
|
Memory function
|
Program Information and SV (Setting Value) backup and restoration, Storage of
Temperature-Humidity setting value and PV
|
■ Touch LCD
|
Model
|
TH300
|
|
Standard
|
TFT LCD 88.9 mm (3.5")
|
|
Resolution
|
320 x RGB x 240
|
|
Life span of back light
|
Edge light L.E.D (Approx. 40,000 hrs)
|
|
Touch type
|
Resistive Operation (4 Wires)
|
|
Language
|
Korean/English
English/Chinese (Simple)
English/Chinese (Traditional)
|
■ Operation Environment
|
Model
|
TH300
|
|
Usable surrounding temperature
|
0 ~ 50 ℃
|
|
Usable surrounding humidity
|
20 ~ 90 % RH (No condensation)
|
|
Storage Temperature
|
-25 ℃ ~ 70 ℃
|
|
Vibration
|
10-55 Hz, amplitude : 0.75 ㎜, 3 directions 4 times, 5 min/cycle
|
|
Shock
|
147 m/s², 3 directions 3 times
|
|
Dimension
|
96 (W) x 96 (H)
|
|
Weight
|
Approx. 0.85 Kg (Including packing materials)
|
▍Suffix Code
Model |
Code |
Description |
TH300 - |
|
|
Programmable Temp.& Humidity Controller / 96(W) x 96(H) x 100(D) |
Communication |
1 |
|
RS232C |
2 |
|
RS485/422 |
Language |
1 |
Korean/English |
2 |
English/Simple Chinese |
3 |
English/Traditional Chinese |
▍Dimension and panel cutout
[Unit : ㎜]
■ Dimension
■ Panel cutout
|