UP-25F Flat type proximity sensor
- Applied exclusive IC for C-MOS.
- Wide range of power supply voltage (5-35 V d.c. : DC 3 wire type)
- Internal noise enhanced circuit.
- Applied the nonpolar two wire type.
- Able to install at metal surface directly Sensing distance 8m, thickness 10.5mm Flat type.
CE

The order from the left is the order in which the information is displayed at the bottom. If you cancel the check, the information will be excluded, and if you check, it will be printed out.

print_icon

▍Specification

■ Inductive DC 3 wire type / 2 wire type

Model

DC 3 wire type

DC 2 wire type

NPN

UP25F-8N□□

Polartiy

UP25F-8T□□

PNP

UP25F-8P□□

Non polarity

UP25F-8U□□

Size

25 x 49 Flat type

25 x 49 Flat type

Appearance

UP25F

Standard sensing object (㎜)

Iron 25 X 25 X 1

Sensing distance

8 mm

Setting distance

0 ~ 6.4 mm

Hysteresis

Less than 10 % of sensing distance

Response frequency

200 Hz

Power supply voltage

12 - 24 V d.c. (Usable voltage range 5 - 35 V d.c.)

12 - 24 V d.c. (Usable voltage range 10 - 30 V d.c.)

ControlOutput

Open/Close

capacitance

200 mA max (Resistive load)

100 mA max (Resistive load)

Residual voltage

Max 1.5 V

Polartiy : max 3.5 V, Non polarity : max 5 V

Current consumption

Max 6 mA

-

Leakage current

-

max 1 mA

Operation indication

Red LED

Protective circuit

Power reversely connected protective circuit, Surge protective circuit and over current protective circuit are built in.

Surge protective circuit, Over current protective circuit are built in.

Degree of protection

IP67(IEC standard)

Connection structure

Cable type (Standard cable length 2m), Connector Cable type

Material

▪Case : PBT resin

▪Cable holder : Polyester elastomer

Certification

CE

Weight

Cable type

approx. 60g

approx. 60g

Relay connector type

approx. 20g

approx. 20g

■ Inductive AC 2 wire type

Model

UP25F-8A□□

Appearance

UP25F

Standard sensing object (㎜)

Iron 25 X 25 X 1

Sensing distance

8 mm

Setting distance

0 ~ 6.4 mm

Hysteresis

Less than 10 % of sensing distance

Response frequency

20 Hz

Power supply voltage

100 - 240 V a.c. (Usable voltage range 90 - 250 V a.c.)

Controloutput

Open/Close

capacitance

200 mA max (Resistive load)

Residual voltage

Max 10 V a.c.

Leakage current

Max 2.2 mA

Operation indication

Red LED

Protective circuit

Surge protective circuit built in.

Degree of protection

IP67 (IEC standard)

Connection structure

Cable type (Standard cable length 2m), Connector Cable type

Material

▪Case : PBT

▪Cable holder : Polyester elastomer

Certification

CE

Weight

Cable type

approx. 60g

Relay connector type

approx. 20g

■ Environment

Ambient temperature

-25 ~ 70 ℃ (Less than ±10 % of sensing distance at temperature 20 ℃)

Ambient humidity

35 ~ 85 % R.H

Insulation resistance

min 50 MΩ (500 V d.c. mega standard) between all terminals and the CASE

Dielectric strength

For 1 min at 2000 V a.c. 50/60 Hz (between the recharging part and case)

Vibration resistance

10 ~ 55 ㎐ (cycle 1 min, Double amplitude : 1.5 ㎜ 2 hours for each of X · Y · Z directions)

Shock resistance

500 m/s² 3 times to each of X · Y · Z directions